3M™ Novec™ Engineered Fluids require little maintenance and offer dependable performance. They have high resistivity and will not damage electronic equipment or integrated circuits in the event of a leak or other failure. They exhibit excellent properties for heat transfer applications:

  • Excellent dielectric properties
  • Wide range of boiling points
  • Good materials compatibility
  • Leaves no residue

They also offer favourable environmental and worker safety properties:

  • Low toxicity
  • Non flammability
  • Low Global Warming Potential (GWP)
  • Zero Ozone Depletion Potential (ODP)

The chemical inertness and non-corrosive properties make them safe for workers to handle. They have been extensively tested to show they are non-irritating to the eyes and skin. They are rated non-hazardous.

3M™ Novec™ Engineered Fluids 7100 and 7200 have been approved for use without restriction under the U.S. EPA’s Significant New Alternatives Policy (SNAP).

700071007200730075007700649
Boiling Point(°C)3461769812816749
Pour Point (°C)-122.5-135-138-38-100-50-108
Global Warming Potential* -GWP37032055200904201
Vapour Pressure(Pa)64.6×10326.8×10315.7×1035.9×1062.1×1030.1×1034.0×103
Density (kg/m3)1400152014201660161017971600
Coefficient of Volume Expansion (K-1)0.002190.00180.0016n/a0.00130.00110.0018
Kinematic Viscosity (cSt)0.320.380.410.710.772.50.4
Absolute Viscosity0.450.580.58n/a1.24n/a0.64
Specific Heat (J kg-1 °C-1)13001180122010161128n/a1103
Heat of Vapourisation @ B.P. (J/g)14211211910188.583.488
Dielectric Strength (kV, 0.1″ gap)~40~40~40~40~40~35>40
Dielectric Constant (1 KHz)7.47.47.3n/a5.86.71.8
Volume Resistivity (ohms/cm)1081081081082×1085×10111×1012